M. HREN et al.: CORROSION PERFORMANCE OF STEEL IN BLENDED CEMENT PORE SOLUTIONS 679–686 CORROSION PERFORMANCE OF STEEL IN BLENDED CEMENT PORE SOLUTIONS KOROZIJSKA ODPORNOST JEKLA V PORNIH VODAH IZ ME[ANIH CEMENTOV Miha Hren 1* , Tadeja Kosec 1 , Andra` Legat 1 , Violeta Bokan-Bosiljkov 2 1 Slovenian National Building and Civil Engineering Institute, Dimi~eva ulica 12, 1000 Ljubljana, Slovenia 2 Faculty of Civil and Geodetic Engineering, Jamova cesta 2, 1000 Ljubljana, Slovenia Prejem rokopisa – received: 2019-01-03; sprejem za objavo – accepted for publication: 2019-04-04 doi:10.17222/mit.2019.003 Blended cements might change the chemistry of the pore solution and subsequently affect the corrosion of steel in concrete. Pore solutions were extracted, analyzed and compared from mortars made of CEM I, CEM II, CEM III and CEM IV cements. Three combinations of carbonation and chloride states were studied, i.e., non-carbonated without chlorides, non-carbonated with chlorides and carbonated with chlorides. Different electrochemical and spectroscopic techniques were used to study the electrochemical properties, the type and the extent of the corrosion products, as well as the type and the extent of the corrosion damage. It was confirmed that the most corrosive environments were pore solutions extracted from the carbonated mortars with chlorides. In this environment the highest corrosion rate was observed for the CEM III pore solution, and the lowest for the CEM I. The extent and the type of corrosion products and the corrosion damage varied according to the environment. Keywords: corrosion, blended cements, pore solution, mortar Cementi z mineralnimi dodatki lahko spremenijo strukturo porne vode in posledi~no vplivajo na korozijske lastnosti jekla. Porne vode so bile iztisnjene in analizirane iz malt, narejenih iz CEM I, CEM II, CEM III in CEM IV cementov. Malte so bile predhodno izpostavljene kloridom ali pospe{eni karbonatizaciji v treh kombinacijah: brez karbonatizacije in brez kloridov, brez karbonatizacije s kloridi in v karbonatizaciji s kloridi. Za ugotavljanje korozijskih lastnosti jekla v pornih vodah so bile uporabljene razli~ne elektrokemijske in spektroskopske metode. Analizirane so bile elektrokemijske lastnosti, tip in obseg korozijskih produktov ter tip in obseg korozijskih po{kodb. Ugotovljeno je bilo, da najbolj korozivno okolje pripada pornim vodam v karbonatizirani malti s kloridi, kjer je bila najvi{ja korozijska hitrost izmerjena v pornih vodah iz CEM III cementa, najmanj{a pa iz CEM I cementa. Obseg in tip korozijskih produktov ter po{kodb se je razlikoval skladno s korozivnostjo okolja. Klju~ne besede: korozija, me{ani cementi, porna voda, malta 1 INTRODUCTION The corrosion of rebar has been a longstanding dura- bility issue in concrete. The penetration of the chloride ions and the reduction in the alkalinity due to carbon- ation can destabilize the passive film that protects the steel from corrosion. The use of certain mineral admix- tures in blended cements affects both corrosion-propaga- tion processes. These mineral admixtures primarily re- fine the concrete pores, which is a well-known beneficial effect that can slow down the chloride penetration and the carbonation progression. 1,2 The same reactions that refine the pores also reduce the alkalinity 3 and affect the chloride binding, 4 thus creating a different and unknown corrosive environment. Multiple corrosion studies have been conducted for mortars or concretes made of blended cements. 5–14 Most of them focus on the additions of silica fume, fly ash and slag, with half-cell potential and linear polarization tech- niques being mostly used to determine the corrosion ac- tivity in the concrete or mortar. All the studies report on blended cements increasing the corrosion resistance due to the latent pozzolanic reaction. However, not a lot of research focuses on aged concrete that has undergone carbonation, nor are there many examples of the corro- sion rates being measured directly. There are many fewer corrosion studies available in concrete pore solutions ex- tracted from blended cements. Most pore-solution exper- iments involved the use of saturated calcium hydroxide, with optional additions of potassium and sodium hydrox- ide. 15–23 Electrochemical impedance spectroscopy and potentiodynamic polarization are the most common tech- niques used in these experiments. While chloride con- centration and alkalinity are the two most important fac- tors influencing steel corrosion, other ions found in the pore solution should not be overlooked. 24 So far, there is no information in the literature as to what extent the pore-solution’s composition influences the corrosion of steel in blended cements. In this paper the effect of the presence of chloride and carbonation was studied on the corrosion behavior of carbon steel in pore solutions extracted from mortars made of blended cements containing different amounts of fly ash, natural pozzolana and slag. Multiple electro- chemical techniques, including corrosion-potential mea- surements, linear polarization and potentiodynamic Materiali in tehnologije / Materials and technology 53 (2019) 5, 679–686 679 UDK 620.193:691.714.018.8:666.9.022.6 ISSN 1580-2949 Original scientific article/Izvirni znanstveni ~lanek MTAEC9, 53(5)679(2019) *Corresponding author's e-mail: miha.hren@zag.si scans, were used to study the corrosion properties. SEM, optical microscopy and Raman spectroscopy were em- ployed to analyze the corrosion products formed in such media. 2 MATERIALS AND METHODS Mortar prisms, 100 mm × 60 mm × 30 mm in size, were made to extract and analyze their pore solutions. Each prism had a water-cement ratio of 0.75 and a ce- ment-aggregate ratio of 0.33. Standard sand, as described in EN 196-1:2016, was used and mixed with one of four different cements: CEM I 42.5 N, CEM II/B-M (LL-V) 42.5 N, CEM III/B (S) 32.5 N – LH/SR and CEM IV/A (V-P) 42.5 R SR. These cements differ in terms of the compressive strength and the admixtures used. Mineral admixtures are designated by the labels in parentheses, with some cements having multiple mineral admixtures. Label V is used for Fly ash, S is used for slag, LL is used for limestone and P is used for natural pozzolans. The cements were provided by a local cement factory, Salonit Anhovo. All the specimens were cured for 28 d in a humidity chamber and one specimen of each cement also under- went accelerated carbonation for 10 w. These specimens are referred to in the text as carbonated, while the natu- rally carbonated specimens are referred to as non-car- bonated. External chlorides were added through a 35-week cyclic ponding of 3.5 % sodium chloride solu- tion, where the wetting period lasted for 3 d and the dry- ing period lasted for 4 d. Reference specimens of each cement were also made to obtain pore water of uncarbonized mortars without external chlorides imme- diately after 28 d of curing in a humidity chamber. The pore solution was extracted from the specimens using an extraction technique described in the litera- ture. 25 A device was used that produces compressive pressure on the specimen in the range of 500 MPa to 1000 MPa and allowed the solution to be drained through a filter. A few ml of solution was extracted, di- luted and analyzed using ion chromatography. Based on these results, a total of 12 synthetic pore solutions were prepared, where the cement type, chlorides and carbon- ation state were varied. All the pore solutions were used as an electrolyte in 3 consecutive electrochemical experiments, with each set of tests repeated at least 3 times with a fresh working electrode and solution. The open-circuit potential (OCP) was measured first for about 22 h, until the potential of the working electrode stabilized. The linear polarization was measured at ±20 mV vs. OCP at a scan rate of 0.1 mV/s. The cyclic polarization followed from –250 mV vs OCP to 1.2 V above the reference potential, or until the current density reached 10 mA/cm 2 . The scan rate was set at 1 mV/s. Tafel fitting was done in Gamry Echem Analyst software to obtain the corrosion poten- tial, the corrosion-current density and both Tafel slopes. In order to obtain the corrosion rates, the corrosion-cur- rent density was first calculated from the linear polarization using the Stern-Geary Equation (1). Anodic ( a ) and cathodic ( c ) Tafel slopes were acquired with the cyclic polarization. The corrosion rates were consecu- tively calculated from the corrosion-current density us- ing Equation (2), where a is the atomic weight of iron (55.8 g/mol), n is the oxidation number of iron (2+) and is the density of the steel (7.9 g/cm 3 ). i R corr ac pa c = ⋅ ⋅+ 2303 .( ) [μm/cm 2 ] (1) CR ai n = ⋅ ⋅ 327 . corr [μm/year] (2) Electrochemical tests were done in Gamry Frame- works using the Gamry Reference 600 potentiostat. All the experiments were performed in a standard three-elec- trode cell, using a saturated calomel reference electrode (SCE), graphite counter electrode and a working elec- trode made of cold-rolled carbon-steel sheet with an ex- posed surface area of 1 cm 2 . All the potentials in the text refer to the SCE potential. Prior to exposure, the steel surface was degreased with acetone and grinded using 600-grit, 1200-grit and 2500-grit papers. Immediately af- ter the 24-hour electrochemical measurements, the elec- trodes were rinsed with distilled water, dried and exam- ined under a Tagarno HD microscope. A low-vacuum JEOL 5500 LV SEM using an accelerating voltage of 20 kV and Horiba Yvon HR800 RAMAN spectrometer with a laser at = 632 nm and scanning range 50 cm –1 to 1000 cm –1 were also used to provide additional information about the surface of the steel and the corrosion products. 3 RESULTS AND DISCUSSION 3.1 Pore water extraction The pore solutions were prepared according to the re- sults of the mortar extraction (Table 1). Components were chosen so that the pH, chloride and sulfate concen- trations (not shown) matched the values of the extracted M. HREN et al.: CORROSION PERFORMANCE OF STEEL IN BLENDED CEMENT PORE SOLUTIONS 680 Materiali in tehnologije / Materials and technology 53 (2019) 5, 679–686 Table 1: Extracted pore solutions. Ion concentrations are in g/L CEMENT AC 1 Cl 2 pH Cl – [Cl – ]/ [OH – ] CEM I 13.06 0.07 0.017 X 12.05 61.04 153 X X 10.45 82.83 8.29×10 3 CEM II 13.03 0.10 0.026 X 11.81 84.86 371 X X 7.52 106.37 9.06×10 6 CEM III 12.51 0.40 0.349 X 11.45 47.99 480 X X 7.54 117.08 9.53×10 6 CEM IV 13.01 0.06 0.017 X 12.06 74.91 184 X X 9.83 109.99 4.59×10 4 1 – Accelerated Carbonation, 2 – External chlorides solutions, while the cations were chosen to reflect the so- lutions as close as possible, due to solubility limitations. All the pH values were measured with a Mettler Toledo MP220 pH meter before and after exposure. They remined stable throughout the electrochemical experi- ments. The pH of the untreated mortars, prepared by using different blended cements (CEM II, CEM III and CEM IV) and standard cement (CEM I) was as high as 13. The pore waters from the mortars that were exposed to cyclic ponding with chlorides contained around 48 g/L to 85 g/L chlorides and the pH was reduced to about 12, while the [Cl – ]/[OH – ] ratio was between 150 and 480. The ac- celerated carbonation and cyclic wetting with chlorides resulted in a very high [Cl – ]/[OH – ] ratio and a substantial decrease of the pH. Carbonation had the least effect on the CEM I pore solution’s alkalinity (around pH 10), fol- lowed by CEM IV, CEM II and CEM III (around pH 7). The CEM III cement had the least amount of lime in its composition, which could be the reason for its lower al- kalinity in all the exposed conditions (Table 1). All the cements showed a much higher chloride concentration after the accelerated carbonation. Although there are not many publications about carbonation and chloride bind- ing, there seems to be a consensus that carbonation re- leases bound chlorides due to the reduction of pores for physical binding and the dissolution of Friedel’s salt due to the lowered alkalinity. 4 The latter would explain the higher concentration of chlorides in all the carbonated blended cements, especially CEM III. When naturally carbonated, CEM II had the largest amount of chlorides in its pore solution, followed by CEM IV, CEM I and CEM III. The chloride-binding capability of a cement is a combination of the alumina content, the C/S ratio, the level of carbonation, the sodium ions present and other factors. 4 If one parameter does not stand out, a combina- tion of all the factors influences the concentration of the bound chlorides. It is hard to determine to what degree each factor contributes to the chloride release. 3.2 Open-circuit potential The open-circuit potential on steel in the pore solu- tions was measured for 22 h. In all the pore waters from the non-carbonated cement without chlorides, the poten- tial increased over time, indicating that the high pH val- ues made the steel more corrosion resistant compared to its in-air state. In some cases, the potential experienced more than a 100-mV drop after being stable for many hours. This may be due to the breakdown processes of the passive film formed in air, as a new, more stable pas- sive film in alkaline solution forms. This process is knowntotakeupto3dinalkaline solutions without ag- gressive ions. 16 Similar trends are rarely observed for ei- ther non-carbonated or carbonated pore water with chlo- rides, as the potential decreased with time and remained relatively stable after a couple hours. The mean OCP error bar chart is shown in Figure 1 at the end of the exposure for pore waters of all 4 ce- ments in the non-carbonated state without chlorides, the non-carbonated state with chlorides and the carbonated state with chlorides. Large differences were observed when comparing the corrosion potentials of the steel in cements in different chloride and carbonation states. The highest potentials were found in the non-carbonated pore water without chlorides, with a potential drop of around 350 mV observed for all the cements as the chlorides were added. The lowest potentials were measured in car- bonated pore water with chlorides. These were between –700 mV and –620 mV. The differences in the corrosion potentials of the steel in different cement types under the same mortar condi- tions were less expressed, but still differentiative. In the non-carbonated state without additional chlorides, the re- sults cannot be correlated to either chloride concentra- tions or alkalinity. However, the highest concentrations of potassium, calcium, magnesium and sulfate ions can be found in the CEM I cement, which could explain its lower and less-stable potential. 19 In the non-carbonated state with additional chlorides, the corrosion potential was the most positive for CEM I, followed by CEM IV and CEM II, while for CEM II it was the lowest (–570 mV). Results in the non-carbonated state with chlorides were in line with the [Cl]/[OH] ratio (Table 1), where a higher ratio is reflected in a lower potential. In the carbonated pore solutions with chlorides, CEM I stood out with its lowest chloride content, highest pH and the resulting highest potential (–640 mV, Figure 1). 3.3 Polarization resistance The results of the polarization resistance (R p ) mea- surements for 4 cements in 3 carbonation and chloride states are presented in Figure 2. The values of R p are shown on a logarithmic scale. The polarization resistance is often translated to the corrosion rate through the Stern-Geary Equation (1) and Equation (2), where a higher polarization resistance results in a lower corrosion rate. M. HREN et al.: CORROSION PERFORMANCE OF STEEL IN BLENDED CEMENT PORE SOLUTIONS Materiali in tehnologije / Materials and technology 53 (2019) 5, 679–686 681 Figure 1: Open circuit potential values for all cements in all exposure states Large differences in the polarization resistance can be seen between the different chloride and carbonation states. In the non-carbonated pore solution without chlo- rides, the polarization resistances were an order of mag- nitude higher for all the cements compared to R p in the non-carbonated pore solution with chlorides. Thus, the corrosion rates in the non-carbonated pore solutions with chlorides were 10-times higher than for the steel in the non-carbonated pore solution without chlorides. The po- larization resistance values between 1.5 k cm 2 and 5 k cm 2 in carbonated pore solutions with chlorides were 2.5-times lower than in the non-carbonated pore solu- tions with chlorides. In the non-carbonated state without external chlo- rides, CEM III had a lower polarization resistance com- pared to the other cements, most likely due to the higher chloride concentration and the lower pH (Table 1). Al- most no differences between the cements could be ob- served in the non-carbonated state with chlorides, apart from CEM II and CEM III having more scattered results. The performance of the cements in the carbonated state with chlorides was in line with the [Cl – ]/[OH – ] ratio, where a higher ratio results in a lower resistance. The CEM III cement had the lowest polarization resistance, followed by CEM II, CEM IV and CEM I. In the carbon- ated state with chlorides, the steel in CEM I had the most positive R p (5 k cm 2 ). 3.4 Cyclic polarization Potentiodynamic scans for the steel in pore solutions simulating the non-carbonated pore solution with and without chlorides and the carbonated pore solution with chlorides are presented in Figure 3. The corrosion-cur- rent density j corr and the corrosion potential E corr were de- duced from the polarization curves and both are pre- sented in Table 2. Using Equation (2), the corrosion rate v corr was calculated from the j corr values. In the non-carbonized pore solution without chlo- rides, the polarization curves showed good corrosion re- sistance for the steel (Figure 3a). The corrosion poten- tial was between –250 mV for CEM I and –130 mV for CEM IV. The corrosion-current densities were similar at 1 μA/cm 2 , and the resulting corrosion rates did not ex- ceed 20 μm/y (Table 2). CEM IV showed the best corro- sion resistance with both the lowest corrosion current and passive current densities (Figure 3a), followed by CEM I, CEM II and CEM III. The steel remained passive in all the pore solutions and the breakdown potential (E b ) was observed at roughly +600 mV vs. SCE, while E b for CEM III was slightly more positive. During the reverse polarization cycle, the currents returned towards zero, following the same path as during anodic polarization. The shape of the potentiodynamic curves showed that no local type of corrosion is expected in such conditions. In the non-carbonized pore solution with chlorides (Figure 3b), the corrosion potentials of the working electrodes were more negative due to the presence of chlorides. The values ranged between –650 mV and –500 mV. In terms of corrosion-current densities and the corresponding corrosion rates, CEM I, II, III and IV showed a similar average value of 3.5 μA/cm 2 (40 μm/y). The breakdown potential for all 4 cement pore solutions was reached at about –300 mV and the repassivation pro- cess required much lower potentials for the current den- sity to reach values in the passive state. This is common for localized, chloride-induced corrosion. After the re- verse polarization cycle, the potentials decreased by about 100 mV, on average. M. HREN et al.: CORROSION PERFORMANCE OF STEEL IN BLENDED CEMENT PORE SOLUTIONS 682 Materiali in tehnologije / Materials and technology 53 (2019) 5, 679–686 Figure 3: Cyclic polarization curves of select specimens in: a) non- carbonated pore water without chlorides, b) non-carbonated pore wa- ter with chlorides and c) carbonated pore water with chlorides Figure 2: Polarization resistance values for all cements in all exposure states CEM IV and CEM I exhibited lower passive current densities compared to CEM II and CEM III (Figure 3b). These results correlate well with the [Cl – ]/[OH – ] ratio, as both CEM II and CEM III have an about 2–3 times higher ratio compared to CEM I and CEM IV. In carbonated pore water with chlorides, the steel un- derwent general corrosion. In the polarization curves (Figure 3c) this was indicated by a lack of a passive re- gion as the current density was increasing with the po- tential in the anodic direction. The corrosion rate was the smallest for CEM I and the highest for CEM II and CEM III (Figure 3c, Table 2). The specimens made of pore water from CEM II, III and IV showed little difference in terms of the average current densities and corrosion rates (Table 2, values around 9 μA/cm 2 and 100 μm/y), with CEM IV having less-scattered results and a lower maxi- mum expected corrosion rate as a result. The CEM I pore water stood out with a noticeably lower average and maximum expected corrosion rate (70±10 μm/y), which is the result of its lower chloride content and higher alka- linity. Its corrosion potential was also higher by about 60 mV, in line with the OPC results. The optical microscopy and SEM images in Figure 5a and 5b of the exposed working electrode in the carbonated pore solution with chlorides showed large areas of uniformly formed corro- sion products. The size of the corroded area was larger when the pH was lower. 3.5 Optical microscopy, SEM and Raman With the aim to follow the development of the corro- sion products, the steel specimens were immersed in three different simulated environments (non-carbonated, non-carbonated with chlorides and carbonated with chlo- rides) of CEM I, CEM II, CEM III and CEM IV pore so- lutions. Only the steel specimens in the most corrosive CEM III environment are presented in Figure 4. The non-carbonated state (pH 12.54) of the CEM III pore so- lution was not aggressive and was observed to have no M. HREN et al.: CORROSION PERFORMANCE OF STEEL IN BLENDED CEMENT PORE SOLUTIONS Materiali in tehnologije / Materials and technology 53 (2019) 5, 679–686 683 Table 2: Corrosion potential, corrosion current and corrosion rate for all cements obtained from cyclic polarization CEMENT E corr [mV] j corr [μA/cm 2 ] v corr [μm/y] non-carbonated no chlorides CEM I –250 ± 50 1.0 ± 0.5 11 ± 5 CEM II –190 ± 30 1.2 ± 0.5 14 ± 5 CEM III –160 ± 40 1.7 ± 0.3 19 ± 4 CEM IV –170 ± 20 0.8 ± 0.3 9 ± 3 non-carbonated chlorides CEM I –590 ± 20 3.0 ± 2.0 40 ± 20 CEM II –580 ± 20 4.0 ± 1.0 40 ± 20 CEM III –590 ± 20 4.0 ± 1.0 40 ± 10 CEM IV –610 ± 40 3.0 ± 2.0 30 ± 20 Carbonated chlorides CEM I –646 ± 1 6.0 ± 1.0 70 ± 10 CEM II –719 ± 9 9.0 ± 5.0 100 ± 50 CEM III –710 ± 10 9.0 ± 5.0 110 ± 50 CEM IV –705 ± 8 9.0 ± 3.0 110 ± 30 Figure 4: Photographs of steel specimen immersed in pore waters extracted from CEM III mortars exposed to different carbonation and chloride states: a) after 7 d, b) and c) after 18 d of exposure and d), e) and f) the same surfaces after cleaning of corrosion products in HCl with urotropine visible signs of corrosion (Figure 4a). In the non-car- bonated state with chlorides (pH 11.46), the corrosion was already visible after 18 d of exposure (Figure 4b), where approximately one-third of the steel surface was covered in corrosion products. Almost the entire exposed surface of the steel was covered in corrosion products (Figure 4c) in the CEM III pore solution that was ex- tracted from carbonated mortars soaked with chlorides (pH 7.50). The corrosion damage is shallow and not lo- calized (Figure 4e and 4f). Optical microscopy and SEM were also used to ex- amine the type of corrosion damage occurring on the specimens in each cement pore solution. No corrosion damage was detected on any of the specimens exposed to non-carbonated pore solutions without chlorides. In the non-carbonated pore solutions with chlorides, large iso- lated pits (CEM I and CEM II) and areas of localized corrosion along the edges of the specimen (CEM III and CEM IV) were detected. Two pits for CEM I and CEM II are shown in Figure 5c and 5d, respectively. The extent and type of damage varied greatly between identical specimens in non-carbonated cements with chlorides, so no generalizations could be made. In the carbonated pore solutions with chlorides, general corrosion was observed for all the cements. Roughly 75 % and 35 % of the ex- posed area was corroded for the CEM I and CEM IV specimens, respectively. In the case of CEM II and CEM III, almost the entire exposed area was corroded (Figure 5a), which is in line with the lower pH values of these pore solutions. SEM and Raman spectroscopy were used to study the morphology and the type of corrosion products present. Similar corrosion products were found across multiple cements’ pore solutions, so only the results from CEM III were evaluated in detail. The Raman spectra of the corrosion products formed on steel were compared to the Raman spectra reported in the literature. 26 On a specimen exposed to a non-carbonized pore solution with chlo- rides, strong hematite and weak goethite spectra were measured (Figure 6a, 6b and 6c). Hematite was charac- terized by two strong bands at 221 cm –1 and 286 cm –1 , one moderate band at 398 cm –1 and two weaker bands at 484 cm –1 and 600 cm –1 . The band around 240 cm –1 was not as pronounced as in the literature. Goethite showed a moderate band at 674 cm –1 and two very weak bands at 238 cm –1 and 387 cm –1 . Both the detected corrosion products are considered stable, adhere to the steel sur- face and slow down the corrosion reaction. 18 The steel specimens in the carbonized pore solution with chlorides predominantly contained lepidocrocite on M. HREN et al.: CORROSION PERFORMANCE OF STEEL IN BLENDED CEMENT PORE SOLUTIONS 684 Materiali in tehnologije / Materials and technology 53 (2019) 5, 679–686 Figure 6: SEM images and Raman spectra of corrosion products found in: a), b) and c) non-carbonated CEM III pore solution with chlorides, d) and e) carbonated CEM III pore solution with chlorides Figure 5: Optical and SEM images after7dofe xposure: a) and b) steel surface in carbonated CEM III pore solution with chlorides, c) pit in non-carbonated CEM I pore solution with chlorides and d) pit in non-carbonated CEM II pore solution with chlorides their surface (Figure 6d and 6e). Lepidocrocite was characterized by two strong bands at 251 cm –1 and 381 cm –1 , and three moderate bands at 530 cm –1 , 649 cm –1 and 713 cm –1 . Unlike goethite and hematite, this phase is unstable and porous. 18 With time, it tends to dissolve and transform to other forms of oxides, thus offering weaker corrosion protection. 4 CONCLUSIONS Pore waters were extracted from 4 cements exposed to a combination of carbonation and chlorides for 35 w. The following conclusions can be drawn. Large differences in the corrosion rates, corrosion po- tentials, corrosion damage and corrosion products were observed when comparing different carbonation and chloride states of the pore solutions. The influence of these states on the corrosion conditions was significantly higher than that of the different cements. When comparing different cement types (CEM I, CEM II, CEM III and CEM IV), it could be observed that the electrochemical properties varied, to some ex- tent. However, these variations could be more significant when taking different degrees of corrosion localization into account. In the non-carbonated state without chlorides the steel in the pore solution from all the cements showed passive behavior, with corrosion current densities as low as 1 μA/cm 2 . The post-exposure microscopic observa- tions confirmed these results. The corrosion damage in all the pore solutions from the carbonated cements with chlorides was roughly gen- eral, whereas the damage in the pore solutions from non-carbonated cements with chlorides was both local- ized and general. Electrochemical techniques generally provided the lowest corrosion rates for CEM I, with the corrosion rates for CEM IV in non-carbonated conditions being somehow comparable to CEM I. The highest corrosion rates overall were measured for CEM III. It should be mentioned, however, that the cor- rosion damage in both the carbonated and non-carbon- ated states with chlorides were roughly general. Spectroscopic analyses of the corrosion products confirmed the electrochemical results. The Raman analy- sis indicated a protective corrosion layer in the non-car- bonated chloride environment and non-protective corro- sion products in the more corrosive carbonated chloride environment. Acknowledgment The financial support received from the Slovenian Research Agency (SRA) during 2015–2017, within the scope of the Young Scientist program, is hereby grate- fully acknowledged. 5 REFERENCES 1 P. K. Mehta, P. J. M. Monteiro, Concrete: microstructure, properties, and materials, McGraw-Hill, New York 2006, 660 2 J. Bijen, Benefits of slag and fly ash, Constr. Build. Mater., 10 (1996) 5, 309–314, doi:10.1016/0950-0618(95)00014-3 3 A. Vollpracht, B. Lothenbach, R. Snellings, J. Haufe, The pore solu- tion of blended cements: a review, Mater. Struct., 49 (2016)8 , 3341–3367, doi:10.1617/s11527-015-0724-1 4 Q. Yuan, C. Shi, G. De Schutter, K. Audenaert, D. Deng, Chloride binding of cement-based materials subjected to external chloride en- vironment – A review, Constr. Build. Mater., 23 (2009) 1, 1–13, doi:10.1016/j.conbuildmat.2008.02.004 5 C. L. Page, N. R. Short, W. R. Holden, The influence of different ce- ments on chloride-induced corrosion of reinforcing steel, Cem. Concr. Res., 16 (1986) 1, 79–86, doi:10.1016/0008-8846(86)90071-2 6 M. Maslehuddin, H. Saricimen, A. I Al-Mana, Effect of fly ash addi- tion on the corrosion resisting characteristics of concrete, ACI Mater. J., 84 (1987), 42-50 7 P. S. Mangat, B. T. Molloy, Influence of PFA, slag and microsilica on chloride induced corrosion of reinforcement in concrete, Cem. Concr. Res., 21 (1991) 5, 819–834, doi:10.1016/0008-8846(91) 90177-J 8 P. S. Mangat, J. M. Khatib, B. T. Molloy, Microstructure, chloride diffusion and reinforcement corrosion in blended cement paste and concrete, Cem. Concr. Compos., 16 (1994) 2, 73–81, doi:10.1016/ 0958-9465(94)90002-7 9 R. B. Polder, W. H. A. Peelen, Characterisation of chloride transport and reinforcement corrosion in concrete under cyclic wetting and drying by electrical resistivity, Cem. Concr. Compos., 24 (2002)5, 427–435, doi:10.1016/S0958-9465(01)00074-9 10 V. Saraswathy, S. Muralidharan, K. Thangavel, S. Srinivasan, Influ- ence of activated fly ash on corrosion-resistance and strength of con- crete, Cem. Concr. Compos., 25 (2003) 7, 673–680, doi:10.1016/ S0958-9465(02)00068-9 11 E. Güneyisi, T. Özturan, M. Gesoðlu, A study on reinforcement cor- rosion and related properties of plain and blended cement concretes under different curing conditions, Cem. Concr. Compos., 27 (2005) 4, 449–461, doi:10.1016/j.cemconcomp.2004.05.006 12 M. A. Ibrahim, A. E.-D. M. Sharkawi, M. M. El-Attar, O. A. Hodhod, Assessing the corrosion performance for concrete mixtures made of blended cements, Constr. Build. Mater., 168 (2018), 21–30, doi:10.1016/j.conbuildmat.2018.02.089 13 N. Chousidis, I. Ioannou, E. Rakanta, C. Koutsodontis, G. Batis, Ef- fect of fly ash chemical composition on the reinforcement corrosion, thermal diffusion and strength of blended cement concretes, Constr. Build. Mater., 126 (2016), 86–97, doi:10.1016/j.conbuildmat.2016. 09.024 14 A. N. Borade, B. Kondraivendhan, Effect of metakaolin and slag blended cement on corrosion behaviour of concrete, IOP Conf. Ser. Mater. Sci. Eng., 216 (2017) 1, 1-6, doi:10.1088/1757-899X/216/ 1/012022 15 R. Liu, L. Jiang, J. Xu, C. Xiong, Z. Song, Influence of carbonation on chloride-induced reinforcement corrosion in simulated concrete pore solutions, Constr. Build. Mater., 56 (2014), 16–20, doi:10.1016/j.conbuildmat.2014.01.030 16 A. Poursaee, C. M. Hansson, Reinforcing steel passivation in mortar and pore solution, Cem. Concr. Res., 37 (2007) 7, 1127–1133, doi:10.1016/j.cemconres.2007.04.005 17 W. Chen, R.-G. Du, C.-Q. Ye, Y.-F. Zhu, C.-J. Lin, Study on the cor- rosion behavior of reinforcing steel in simulated concrete pore solu- tions using in situ Raman spectroscopy assisted by electrochemical techniques, Electrochimica Acta., 55 (2010) 20, 5677–5682, doi:10.1016/j.electacta.2010.05.003 18 J. K. Singh, D. D. N. Singh, The nature of rusts and corrosion char- acteristics of low alloy and plain carbon steels in three kinds of con- M. HREN et al.: CORROSION PERFORMANCE OF STEEL IN BLENDED CEMENT PORE SOLUTIONS Materiali in tehnologije / Materials and technology 53 (2019) 5, 679–686 685 crete pore solution with salinity and different pH, Corros. Sci. 56 (2012) 129–142. doi:10.1016/j.corsci.2011.11.012. 19 P. Ghods, O. B. Isgor, G. McRae, T. Miller, The effect of concrete pore solution composition on the quality of passive oxide films on black steel reinforcement, Cem. Concr. Compos. 31 (2009) 2–11. doi:10.1016/j.cemconcomp.2008.10.003. 20 M. Moreno, W. Morris, M. G. Alvarez, G. S. Duffó, Corrosion of re- inforcing steel in simulated concrete pore solutions: Effect of carbon- ation and chloride content, Corros. Sci., 46 (2004), 2681–2699, doi:10.1016/j.corsci.2004.03.013 21 F. Zhang, J. Pan, C. Lin, Localized corrosion behaviour of reinforce- ment steel in simulated concrete pore solution, Corros. Sci., 51 (2009) 9, 2130–2138, doi:10.1016/j.corsci.2009.05.044 22 A. ^esen, T. Kosec, A. Legat, V. Bokan-Bosiljkov, Corrosion proper- ties of different forms of carbon steel in simulated concrete pore wa- ter, Mater. Tehnol., 48 (2014) 1, 51–57 23 G. Liu, Y. Zhang, Z. Ni, R. Huang, Corrosion behavior of steel sub- mitted to chloride and sulphate ions in simulated concrete pore solu- tion, Constr. Build. Mater., 115 (2016), 1–5, doi:10.1016/ j.conbuildmat.2016.03.213 24 A. Poursaee, C. M. Hansson, Potential pitfalls in assessing chlo- ride-induced corrosion of steel in concrete, Cem. Concr. Res., 39 (2009) 5, 391–400, doi:10.1016/j.cemconres.2009.01.015 25 M. Cyr, P. Rivard, F. Labrecque, A. Daidi}, High-pressure device for fluid extraction from porous materials: Application to cement-based materials, J. Am. Ceram. Soc., 91 (2008) 8, 2653–2658, doi:10.1111/j.1551-2916.2008.02525.x 26 F. Dubois, C. Mendibide, T. Pagnier, F. Perrard, C. Duret, Raman mapping of corrosion products formed onto spring steels during salt spray experiments. A correlation between the scale composition and the corrosion resistance, Corros. Sci., 50 (2008) 12, 3401–3409, doi:10.1016/j.corsci.2008.09.027 M. HREN et al.: CORROSION PERFORMANCE OF STEEL IN BLENDED CEMENT PORE SOLUTIONS 686 Materiali in tehnologije / Materials and technology 53 (2019) 5, 679–686